196 Parameters
Defines the minimum value of frequency output 1. See
diagrams at parameter
0 Hz
0…16000 Hz
Minimum value of frequency output 1.
1 = 1 Hz
Defines the maximum value of frequency output 1. See
diagrams at parameter
16000 Hz
0…16000 Hz
Maximum value of frequency output 1.
1 = 1 Hz
Defines a filtering time for parameter
. The
filtering time will only affect the DIOs that are in input mode.
10.0 ms
0.3 … 100.0 ms
Filtering time for
.
10 = 1 ms
12
Configuration of standard analog inputs.
Triggers the analog input tuning function.
Connect the signal to the input and select the appropriate
tuning function.
No action
AI tune is not activated.
0
AI1 min tune
Current analog input AI1 signal value is set as minimum value
of AI1 into parameter
. The value reverts back
to
automatically.
1
AI1 max tune
Current analog input AI1 signal value is set as maximum
value of AI1 into parameter
. The value reverts
automatically.
2
AI2 min tune
Current analog input AI2 signal value is set as minimum value
of AI2 into parameter
. The value reverts back
to
automatically.
3
AI2 max tune
Current analog input AI2 signal value is set as maximum
value of AI2 into parameter
. The value reverts
automatically.
4
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the
limits. For example, if the maximum limit for the input is
7.000 V, the maximum limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by
parameter
Note:
Analog input signal supervision is only active when
• the analog input is set as the source (using the
selection) in parameter
,
,
,
,
,
, and is being used as the active source, or
• supervision is forced using parameter
.
No action
No action taken.
0
Fault
Drive trips on
.
1
Warning
Drive generates an
warning.
2
Last speed
Drive generates a warning (
) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...