Parameters 371
49
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note:
For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
is taken.
10.0 s
0.3 … 3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
Selects how the drive reacts to a control panel (or PC tool)
communication break.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
See also parameters
No action
No action taken.
0
Fault
Drive trips on
. This only occurs if
control is expected from the control panel (it is selected as
source of start/stop/reference in the currently active control
location), or if supervision is forced using parameter
1
Last speed
Drive generates an
warning and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the control panel, or if
supervision is forced using parameter
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and sets
the speed to the speed defined by parameter
(or
when frequency reference
is being used). This only occurs if control is expected from the
control panel, or if supervision is forced using parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...