![ABB ACS880-01 Series Скачать руководство пользователя страница 580](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621580.webp)
580 Fault tracing
A7AB
Extension I/O
configuration failure
The I/O extension module
types and locations specified
by parameters do not match
the detected configuration.
Check the auxiliary code. The code
indicates which I/O extension module is
affected.
Check the type and location settings of
the modules (parameters
Check that the modules are properly
installed.
A7B0
Motor speed feedback
Programmable warning:
No motor speed feedback is
received.
Check the auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the
encoder interface module (
01
:
02
), “YY”
specifies the encoder (
01:
,
02:
). “ZZZZ” indicates the
problem (see actions for each code
below).
0001 Motor gear definition invalid or
outside limits.
Check motor gear settings (
and
0002 Encoder not configured.
Check encoder settings (
).
) to validate any changes in the
settings.
0003 Encoder stopped working.
Check encoder status.
0004 Encoder drift detected.
Check for slippage between encoder and
motor.
A7B1
Load speed feedback
Programmable warning:
No load speed feedback is
received.
Check the auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the
encoder interface module (
01
:
02
), “YY”
specifies the encoder (
01:
,
02:
). “ZZZZ” indicates the
problem (see actions for each code
below).
0001 Load gear definition invalid or
outside limits.
Check load gear settings (
and
0002 Feed constant definition invalid
or outside limits.
Check feed constant settings (
and
0003 Encoder stopped working.
Check encoder status.
A7C1
FBA A communication
Programmable warning:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
and
.
Check cable connections.
Check if communication master is able to
communicate.
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...