![ABB ACS880-01 Series Скачать руководство пользователя страница 300](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621300.webp)
300 Parameters
Enables the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise
to the overvoltage control limit. To prevent the DC voltage
from exceeding the limit, the overvoltage controller
automatically decreases the braking torque.
Note:
If the drive is equipped with a brake chopper and
resistor, or a regenerative supply unit, the controller must be
disabled.
Disable
Overvoltage control disabled.
0
Enable
Overvoltage control enabled.
1
Enables the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the motor
torque in order to keep the voltage above the lower limit. By
decreasing the motor torque, the inertia of the load will cause
regeneration back to the drive, keeping the DC link charged
and preventing an undervoltage trip until the motor coasts to
a stop. This will act as a power-loss ride-through functionality
in systems with high inertia, such as a centrifuge or a fan.
Disable
Undervoltage control disabled.
0
Enable
Undervoltage control enabled.
1
(Only visible when IGBT supply unit control activated by
Displays limit word 1 of the supply unit.
This parameter is read-only.
-
0000h…FFFFh
Supply unit limit word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
P user ref max
1 = Power reference is being limited by supply control program
parameters
1
P user ref min
2
P user max
1 = Power is being limited by parameter
3
P user min
1 = Power is being limited by parameter
4
P cooling
overtemp
1 = Power reference is being limited because of coolant
overtemperature
5
P power unit
overtemp
1 = Power reference is being limited because of supply unit
overtemperature
6…15
Reserved
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...