Parameters 477
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING!
After switching any bits in this word,
recheck the values of the affected parameters.
-
0000h…FFFFh
Hardware options configuration word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Supply frequency
60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters
,
,
,
1
Emergency stop
Cat 0
1 = Emergency stop, Category 0, without FSO module. Affects
.
2
Emergency stop
Cat 1
1 = Emergency stop, Category 1, without FSO module. Affects
.
3
RO2 for -07
cabinet cooling fan
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects
.
4
Externally powered
control unit
1 = Control unit powered externally. Affects
.
(Only visible with
a ZCU control unit)
5
DC supply switch
1 = DC switch monitoring active. Affects
(Only
visible with a ZCU control unit)
6
DOL motor switch 1 = Motor fan control active. Affects
,
7
xSFC-01 fuse
switch controller
1 = xSFC charging controller used. Affects
.
(Only visible with a
BCU control unit)
8
Service switch
1 = Service switch connected. Affects
9
Output contactor
1 = Output contactor present. Affects
,
.
10
Brake resistor, sine
filter, IP54 fan
1 = Status (eg. thermal) switches connected to DIIL input. Affects
11
INU-DSU
communication
1 = Diode supply unit control by inverter unit active. Makes several
parameters visible in groups
,
12
Reserved
13
du/dt filter
activation
1 = Active: An external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
Note:
This bit is to be left at 0 if the drive/inverter module is
equipped with internal du/dt filtering (for example, frame R8i inverter
modules with E205).
14
DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
line cooling fans (C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
15
INU-ISU
communication
1 = IGBT supply unit control by inverter unit active. Makes several
parameters visible in groups
,
,
,
and
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...