590 Fault tracing
4000
Motor cable overload
Calculated motor cable
temperature has exceeded
warning limit.
Check the settings of parameters
Check the dimensioning of the motor
cable in regard to required load.
4210
IGBT overtemperature Estimated drive IGBT
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4290
Cooling
Drive module temperature is
excessive.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate
Hardware manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
42F1
IGBT temperature
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4310
Excess temperature
Power unit module
temperature is excessive.
See
(page
4380
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases.
See
(page
).
4381
PCB space cooling
Temperature difference
between ambient and drive
module PCB space is
excessive.
See
(page
4981
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter
.
4982
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter
.
4990
FPTC not found
A thermistor protection module
has been activated by
parameter
but cannot be
detected.
Power down the control unit and make
sure that the module is properly inserted
in the correct slot.
The last digit of the auxiliary code
identifies the slot.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...