570 Fault tracing
A2BA
IGBT overload
Excessive IGBT junction to
case temperature. This
warning protects the IGBT(s)
and can be activated by a short
circuit in the motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
A3A1
DC link overvoltage
Intermediate circuit DC voltage
too high (when the drive is
stopped).
Check the supply voltage setting
(parameter
). Note
that the wrong setting of the parameter
may cause the motor to rush
uncontrollably, or may overload the brake
chopper or resistor.
Check the supply voltage.
With A3A1 or A3A2 on parallel-
connected inverter modules, the auxiliary
code indicates the affected module. The
format of the code is 000X XX00, where
“XXX” specifies the channel on the BCU
control unit.
If the problem persists, contact your local
ABB representative.
A3A2
DC link undervoltage
Intermediate circuit DC voltage
too low (when the drive is
stopped).
A3AA
DC not charged
The voltage of the intermediate
DC circuit has not yet risen to
operating level.
A480
Motor cable overload
Calculated motor cable
temperature has exceeded
warning limit.
Check the settings of parameters
Check the dimensioning of the motor
cable in regard to required load.
A490
Incorrect temperature
sensor setup
Problem with motor
temperature measurement.
Check the auxiliary code (format 0XYY
ZZZZ).
“X” identifies the affected temperature
monitoring function (0 = parameter
,
1 = parameter
“YY” indicates the selected temperature
source, ie. the setting of the selection
parameter in hexadecimal.
“ZZZZ” indicates the problem (see
actions for each code below).
0001 Sensor type mismatch
Check parameters
/
against
0002 Temperature under limit
Check parameters
…
(and
encoder interface).
Check the sensor and its wiring.
0003 Short circuit
0004 Open circuit
A491
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded warning limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
A492
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded warning limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...