Fault tracing 575
1 Slip frequency is too small
Check the settings of the motor
configuration parameters in groups 98
and 99.
Check that the drive is sized correctly for
the motor.
2 Synchronous and nominal
speeds differ too much
3 Nominal speed is higher than
synchronous speed with 1 pole
pair
4 Nominal current is outside
limits
5 Nominal voltage is outside
limits
6 Nominal power is higher than
apparent power
7 Nominal power not consistent
with nominal speed and torque
A6A5
No motor data
Parameters in group 99 have
not been set.
Check that all the required parameters in
group 99 have been set.
Note:
It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
A6A6
Supply voltage
unselected
The supply voltage has not
been defined.
Set supply voltage in parameter
A6B0
User lock is open
The user lock is open, ie. user
lock configuration parameters
are visible.
Close the user lock by entering an invalid
pass code in parameter
).
A6B1
User pass code not
confirmed
A new user pass code has
been entered in parameter
but not confirmed in
Confirm the new pass code by entering
the same code in
. To cancel,
close the user lock without confirming the
new code. See section
(page
).
A6D1
FBA A parameter
conflict
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
and
.
A6D2
FBA B parameter
conflict
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
and
.
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...