Parameters 265
Defines the zero frequency of the resonance frequency filter.
The value must be set near the resonance frequency, which
is filtered out before the speed controller.
The drawing shows the frequency response.
45.00 Hz
0.50 … 500.00 Hz
Zero frequency.
1 = 1 Hz
Defines the damping coefficient for parameter
. The
value of 0 corresponds to the maximum elimination of the
resonance frequency.
Note:
To ensure that the resonance frequency band is filtered
(rather than amplified), the value of
must be smaller
than
0.000
-1.000 … 1.000
Damping coefficient.
100 = 1
No.
Name/Value
Description
Def
/
FbEq16
20
20log
10
|
H
(
ω
)|
f
(Hz)
0
-20
-40
-60
50
100
0
150
20
20log
10
|
H
(
ω
)|
f
(Hz)
f
zero
= 45 Hz
ξ
zero
= 0.250
ξ
pole
= 1
f
zero
= 45 Hz
ξ
zero
= 0
ξ
pole
= 1
0
-20
-40
-60
50
100
0
150
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...