![ABB ACS880-01 Series Скачать руководство пользователя страница 466](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621466.webp)
466 Parameters
Enable
Estimated position used. (Uses position interpolation;
extrapolated at the time of data request.)
1
(Visible when an absolute encoder is selected)
Defines the number of bits used to indicate position within
one revolution. For example, a setting of 15 bits corresponds
to 32768 positions per revolution.
The value is used when parameter
is set to
,
. When parameter
is set to
parameter is internally set to 17.
Note:
With an EnDat or HIPERFACE encoder and FEN-11
FPGA version VIE12200 or later, this parameter is
automatically set upon validation of encoder settings (
0
0…32
Number of bits used in position indication within one
revolution.
1 = 1
(Visible when a TTL, TTL+ or HTL encoder is selected)
Selects whether calculated or estimated speed is used.
Estimation increases the speed ripple in steady state
operation, but improves the dynamics.
Note:
This parameter is not effective with FEN-xx modules
with FPGA version VIEx 2000 or later.
Disable
Last calculated speed used. (The calculation interval is 62.5
microseconds to 4 milliseconds.)
0
Enable
Estimated speed (estimated at the time of data request) is
used.
1
(Visible when an absolute encoder is selected)
Defines the number of bits used in revolution counting with a
multiturn encoder. For example, a setting of 12 bits would
support counting up to 4096 revolutions.
The value is used when parameter
is set to
,
. When parameter
is set to
, setting
this parameter to a non-zero value activates multiturn data
requesting.
Note:
With an EnDat or HIPERFACE encoder and FEN-11
FPGA version VIE12200 or later, this parameter is
automatically set upon validation of encoder settings (
0
0…32
Number of bits used in revolution count.
1 = 1
(Visible when a TTL, TTL+ or HTL encoder is selected)
Activates transient filtering for the encoder (changes in
direction of rotation are ignored above the selected pulse
frequency).
4880 Hz
Change in direction of rotation allowed below 4880 Hz.
0
2440 Hz
Change in direction of rotation allowed below 2440 Hz.
1
1220 Hz
Change in direction of rotation allowed below 1220 Hz.
2
Disabled
Change in direction of rotation allowed at any pulse
frequency.
3
or
Selects the power supply voltage for encoder 1.
0V
Disabled.
0
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...