Parameters 325
KTY84 analog I/O
KTY84 sensor connected to the analog input selected by
parameter
and an analog
output. The input and output can be on the drive control unit
or on an extension module.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the unit selection parameter of the input to volt.
• Set the source selection parameter of the analog output to
“
• Select the analog input in parameter
. In case the
input is located on an I/O extension module, use the
selection
to point at the actual input value parameter
(for example,
The analog output feeds a constant current through the
sensor. As the resistance of the sensor changes along with its
temperature, the voltage over the sensor changes. The
voltage is read by the analog input and converted into
degrees.
2
KTY84 encoder
module 1
KTY84 sensor connected to encoder interface 1.
See also parameters
3
KTY84 encoder
module 2
KTY84 sensor connected to encoder interface 2.
See also parameters
4
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog input selected
by parameter
output. The input and output can be on the drive control unit
or on an extension module.
The required settings are the same as with selection
, except that the source selection parameter of the
analog output must be set to
5
2 × Pt100 analog
I/O
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 × Pt100 analog
I/O
As selection
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
PTC DI6
PTC sensor connected to digital input DI6 (see the
connection diagram on page
).
Note:
Either 0 ohm (normal temperature) or 4000 ohm
(excessive temperature) will be shown by
. By default, an excessive temperature will
generate a warning as per parameter
. If you want a fault instead, set
to 4000 ohm.
8
PTC analog I/O
PTC sensor connected to a standard analog input selected by
parameter
and an analog
output. The input and output can be on the drive control unit
or on an extension module.
The required settings are the same as with selection
, except that the source selection parameter of the
analog output must be set to
.
20
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...