![ABB ACS880-01 Series Скачать руководство пользователя страница 350](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621350.webp)
350 Parameters
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
Source selection (see
). -
Defines the start limit for the sleep function when parameter
is set to
0.0
0.0 … 32767.0
Sleep start level.
1 = 1
Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep condition selected by
parameter
becomes true, and resets
if the condition becomes false.
60.0 s
0.0 … 3600.0 s
Sleep start delay.
1 = 1 s
Defines a boost time for the sleep boost step. See parameter
.
0.0 s
0.0 … 3600.0 s
Sleep boost time.
1 = 1 s
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
.
If active, sleep boost is aborted when the drive wakes up.
0.0
0.0 … 32767.0
Sleep boost step.
1 = 1
When
, this
parameter defines the wake-up level as deviation between
process setpoint and feedback. The unit is selected by
parameter
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (
), the drive wakes up.
See also parameter
.
0.00 rpm, %
or Hz
-32768.00 …
32767.00 rpm, % or
Hz
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1 unit
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
The delay timer starts when the deviation exceeds the wake-
up level (
), and resets if the
deviation falls below the wake-up level.
0.50 s
0.00 … 60.00 s
Wake-up delay.
1 = 1 s
Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter
is substituted for the PID controller
1 = Tracking mode enabled
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...