Parameters 395
Sets a timeout for master/follower (DDCS) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
is taken.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
100 ms
0…65535 ms
Master/follower communication timeout.
Selects how the drive reacts to a master/follower
communication break.
No action
No action taken.
0
Warning
The drive generates an
warning. This
only occurs if control is expected from the master/follower
link, or if supervision is forced using parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
1
Fault
Drive trips on
. This only occurs if control
is expected from the master/follower link, or if supervision is
forced using parameter
.
2
Fault always
Drive trips on
. This occurs even though
no control is expected from the master/follower link.
3
Selects the type and scaling of reference 1 received from the
master/follower link. The resulting value is shown by
.
Auto
Type and scaling are chosen automatically according to
which reference chain (see settings
) the incoming reference is connected to. If the
reference is not connected to any chain, no scaling is applied
(as with setting
0
Transparent
No scaling is applied.
1
General
Generic reference with a scaling of 100 = 1 (ie. integer and
two decimals).
2
Torque
The scaling is defined by parameter
3
Speed
The scaling is defined by parameter
.
4
Frequency
The scaling is defined by parameter
. 5
Selects the type and scaling of reference 2 received from the
master/follower link. The resulting value is shown by
.
For the selections, see parameter
.
Selects the type/source and scaling of actual value ACT1
transmitted to the master/follower link.
Auto
Type/source and scaling follow the type of reference 1
selected by parameter
. See the individual
settings below for the sources and scalings.
0
Transparent
Reserved.
1
General
Reserved.
2
Torque
is sent as actual value 1. The scaling is
.
3
Speed
is sent as actual value 1. The scaling
is defined by parameter
4
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...