![ABB ACS880-01 Series Скачать руководство пользователя страница 581](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621581.webp)
Fault tracing 581
A7C2
FBA B communication
Programmable warning:
Cyclical communication
between drive and fieldbus
adapter module B or between
PLC and fieldbus adapter
module B is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter group
.
Check cable connections.
Check if communication master is able to
communicate.
A7CA DDCS controller
comm loss
Programmable warning:
DDCS (fiber optic)
communication between drive
and external controller is lost.
Check status of controller. See user
documentation of controller.
Check settings of parameter group
.
Check cable connections. If necessary,
replace cables.
A7CB MF comm loss
Programmable warning:
Master/follower
communication is lost.
Check the auxiliary code. The code
indicates which node address (defined by
parameter
in each drive) on the
master/follower link is affected.
Check settings of parameter group
.
On the FDCO module (if present), check
that the DDCS link switch is not set to 0
(OFF).
Check cable connections. If necessary,
replace cables.
A7CE EFB comm loss
Programmable warning:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
A7E1
Encoder
Programmable warning:
Encoder error.
Check the auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the
encoder interface module (
01
:
,
02
:
), “YY”
specifies the encoder (
01:
02:
). “ZZZZ” indicates the
problem (see actions for each code
below).
0001 Cable fault
Check the conductor order at both ends
of the encoder cable.
Check the groundings of the encoder
cable.
If the encoder was working previously,
check the encoder, encoder cable and
encoder interface module for damage.
See also parameter
0002 No encoder signal
Check the condition of the encoder.
0003 Overspeed
Contact your local ABB representative.
0004 Overfrequency
Contact your local ABB representative.
0005 Resolver ID run failed
Contact your local ABB representative.
0006 Resolver overcurrent fault
Contact your local ABB representative.
0007 Speed scaling error
Contact your local ABB representative.
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...