378 Parameters
Selects how the drive reacts upon a fieldbus communication
break. A time delay for the action can be defined by
parameter
See also parameter
No action
No action taken.
0
Fault
. This only
occurs if control is expected from the FBA B interface (FBA B
selected as source of start/stop/reference in the currently
active control location), or if supervision is forced using
parameter
1
Last speed
Drive generates an
warning and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the FBA B interface, or
if supervision is forced using parameter
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and
sets the speed to the value defined by parameter
(when speed reference is being used) or
(when frequency reference is being
used). This only occurs if control is expected from the FBA B
interface, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Fault always
Drive trips on
. This occurs even
though no control is expected from the FBA B interface.
4
Warning
Drive generates an
warning.
This occurs even though no control is expected from the
fieldbus. This only occurs if control is expected from the FBA
B interface, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
5
Defines the time delay before the action defined by parameter
is taken. Time count starts when
the communication link fails to update the message.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
0.3 s
0.3 … 6553.5 s
Time delay.
1 = 1 s
Selects the type and scaling of reference 1 received from
fieldbus adapter B.
See parameter
Selects the type and scaling of reference 2 received from
fieldbus adapter B.
See parameter
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus adapter
B.
See parameter
.
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...