Fault tracing 593
5692
PU board powerfail
Power unit power supply
failure.
Check the auxiliary code (format
ZZZY YYXX). “YY Y” specifies the
affected inverter module (
0…C
, always
0
for ZCU control units). “XX” specifies the
affected power supply (
1:
Power supply
1,
2:
Power supply 2,
3:
both supplies).
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact your local ABB representative,
quoting the auxiliary code.
5694
PU communication
configuration
Number of connected power
modules differs from expected.
Check setting of
. Cycle the power to
the drive. If the control unit is externally
powered, also reboot the control unit
(using parameter
) or by cycling its power.
If the problem persists, contact your local
ABB representative.
5695
Reduced run
Number of inverter modules
detected does not match the
value of parameter
.
Check that the value of
corresponds to the number of
inverter modules present. Check that the
modules present are powered from the
DC bus and connected by fiber optic
cables to the BCU control unit.If all
modules of the inverter unit are in fact
available (eg. maintenance work has
been completed), check that parameter
is set to 0 (reduced run function
disabled).
5696
PU state feedback
State feedback from output
phases does not match control
signals.
Contact your local ABB representative,
quoting the auxiliary code.
5697
Charging feedback
Incorrect parameter setting.
Check the setting of
. The parameter should be
enabled only if an xSFC charging
controller is installed.
The charging switch and DC
switch were operated out of
sequence, or a start command
was issued before the unit was
ready.
The normal power-up sequence is:
1. Close charging switch.
2. After charging finishes (charging OK
lamp lights), close DC switch.
3. Open charging switch.
Charging circuit fault.
Check the charging circuit.
With a frame R6i/R7i inverter module, the
auxiliary code “FA” indicates that the
charging contactor status feedback does
not match the control signal.
With parallel-connected frame R8i
modules, the auxiliary code (format
XX00), “XX” specifies the affected BCU
control unit channel.
5698
Unknown power unit
fault
Unidentified power unit logic
fault.
Check power unit logic and firmware
compatibility.
Contact your local ABB representative.
6000
Internal SW error
Internal error.
Contact your local ABB representative,
quoting the auxiliary code.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...