Fault tracing 579
A79C
BC IGBT excess
temperature
Brake chopper IGBT
temperature has exceeded
internal warning limit.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameters
Check minimum allowed resistor value
for the chopper being used.
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
A7A1
Mechanical brake
closing failed
Programmable warning:
Status of mechanical brake
acknowledgement is not as
expected during brake close.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
.
Check that acknowledgement signal
matches actual status of brake.
A7A2
Mechanical brake
opening failed
Programmable warning:
Status of mechanical brake
acknowledgement is not as
expected during brake open.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
.
Check that acknowledgement signal
matches actual status of brake.
A7A5
Mechanical brake
opening not allowed
Programmable warning:
Open conditions of mechanical
brake cannot be fulfilled (for
example, brake has been
prevented from opening by
parameter
).
Check mechanical brake settings in
parameter group
(especially
).
Check that acknowledgement signal (if
used) matches actual status of brake.
A7AA Extension AI
parameterization
The hardware current/voltage
setting of an analog input (on
an I/O extension module) does
not correspond to parameter
settings.
Check the auxiliary code (format
XX00 00YY). “XX” specifies the number
of the I/O extension module (
01:
02:
03:
). “YY”
specifies the analog input on the module.
For example, in case of I/O extension
module 1, analog input AI1 (auxiliary
code 0000 0101), the hardware
current/voltage setting on the module is
shown by parameter
. The
corresponding parameter setting is
. Adjust either the hardware setting
on the module or the parameter to solve
the mismatch.
Note:
Control board reboot (either by
cycling the power or through parameter
) is required to
validate any changes in the hardware
settings.
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...