Parameters 301
(Only visible when IGBT supply unit control activated by
Displays limit word 2 of the supply unit.
This parameter is read-only.
-
0000h…FFFFh
Supply unit limit word 2.
1 = 1
(Only visible when IGBT supply unit control activated by
Displays limit word 3 of the supply unit.
This parameter is read-only.
-
0000h…FFFFh
Supply unit limit word 3.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Q user ref max
1 = Reactive power reference is being limited
1
Q user ref min
2
Q cooling
overtemp
1 = Reactive power reference is being limited because of coolant
overtemperature
3
Q power unit
overtemp
1 = Reactive power reference is being limited because of supply unit
overtemperature
4
AC overvoltage
1 = AC overvoltage protection
5…6
Reserved
7
AC diff max
1 = (When AC voltage-type reactive power reference is being used)
Input of AC control is being limited
8
AC diff min
9…15
Reserved
Bit
Name
Description
0
Undervoltage
limit
1 = Power is being limited by the undervoltage controller
1
Overvoltage limit 1 = Power is being limited by the overvoltage controller
2
Motoring power
1 = Power is being limited by temperature or user power limits (see
parameters
)
3
Generating
power
4
Active current
limit
1 = Active current is being limited. For details, see bits 6…9 and
14…15.
5
Reactive current
limit
1 = Reactive current is being limited. For details, see bits 12…13.
6
Thermal limit
1 = Active current is being limited by internal main circuit thermal limit
7
SOA limit
1 = Active current is being limited by internal safe operation area limit
8
User current limit 1 = Active current is being limited by current limit set by supply control
program parameters
9
Thermal IGBT
1 = Active current is being limited based on internal maximum thermal
IGBT stress limit
10…11 Reserved
12
Q act neg
1 = Negative reactive current is being limited by maximum total current
13
Q act pos
1 = Positive reactive current is being limited by maximum total current
14
P act neg
1 = Negative active current is being limited by maximum total current
15
P act pos
1 = Positive reactive current is being limited by maximum total current
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...