Fault tracing 583
A889
Edge counter 2
(Editable message text)
Programmable warning:
Warning generated by edge
counter 2.
Check the source of the warning
(parameter
).
A88A
Value counter 1
(Editable message text)
Programmable warning:
Warning generated by value
counter 1.
Check the source of the warning
(parameter
).
A88B
Value counter 2
(Editable message text)
Programmable warning:
Warning generated by value
counter 2.
Check the source of the warning
(parameter
).
A88C
Device clean
Warning generated by an on-
time timer.
Programmable warnings:
Check the auxiliary code. Check the
source of the warning corresponding to
the code:
0:
1:
10:
A88D
DC capacitor
A88E
Cabinet fan
A88F
Cooling fan
A890
Additional cooling
A8A0
AI supervision
Programmable warning:
An analog signal is outside the
limits specified for the analog
input.
Check the auxiliary code (format XYY).
“X” specifies the location of the input (
0
:
AI on control unit;
1
: I/O extension
module 1, etc.), “YY” specifies the input
and limit (
01:
AI1 under minimum,
02:
AI1 over maximum,
03:
AI2 under
minimum,
04:
AI2 over maximum).
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
A8B0
Signal supervision
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision 1 function.
Check the source of the warning
(parameter
A8B1
Signal supervision 2
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision 2 function.
Check the source of the warning
(parameter
A8B2
Signal supervision 3
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision 3 function.
Check the source of the warning
(parameter
A8BE ULC overload warning
Programmable fault:
Selected signal has exceeded
the user overload curve.
Check for any operating conditions
increasing the monitored signal (for
example, the loading of the motor if the
torque or current is being monitored).
Check the definition of the load curve
(parameter group
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...