![ABB ACS880-01 Series Скачать руководство пользователя страница 445](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621445.webp)
Parameters 445
Defines the source for the supervision high signal.
The value of this parameter is then compared with the limit
set in parameter
If the observed signal is greater than the limit for the time
period set in parameter
, then
the current cleaning step is interrupted. Cleaning sequence
will proceed for the off-time and then switch to the next
cleaning step. The supervision high is not active during the
off-time period.
Note:
For the Supervision High function to work, parameter
, bit-12 must be set to 1.
NULL
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
FBA1 ref
See parameter
(page
).
3
FBA2 ref
See parameter
(page
).
4
EFB1 ref
See parameter
(page
).
5
EFB2 ref
See parameter
(page
).
6
Estimated motor
current
Parameter
(see page
7
Motor current%
Estimated motor current in % of nominal motor current.
8
). -
Defines low limit value for the Supervision high function.
See parameter
.
0.00
0.00...30000.00
Supervision high limit.
10 = 1
Defines delay time for the Supervision high function.
See parameter
.
10.0
0.0...3200.0 s
Supervision high delay.
10 = 1s
Defines the control program response event type in case the
actual amount of cleaning operation exceeds the defined limit
set in parameter
in period of time
set in parameter
.
Not selected
Cleaning maximum event is not selected.
0
Warning
Cleaning maximum event generates a warning.
1
Fault
Cleaning maximum event generates a fault.
2
Defines maximum allowed quantity of cleaning operations in
time period set in parameter
0
0...100
Maximum cleaning amount.
1 = 1
Defines the time window span for the function which monitors
the number of cleaning operations.
0.00
0.00...650.00 hour
Cleaning maximum period in hours.
100 = 1hour
Displays active speed reference from the cleaning function.
0.00
-1200.00...
1200.00 %
Cleaning reference.
10 = 1%
Displays the time elapsed since last cleaning operation was
completed.
00 00:00
00:00:00...90 00:00
Elapsed time since last cleaning.
-
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...