YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
35
No.
(Hex.)
Name
Description
Default
(Range)
–
When 8: Full/Auto
, port 1 is set to Full and port 2 is set to Auto.
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed (Port 1/Port 2).
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
F7-15
is only effective when the port is set to half or full duplex in
F7-14 [Duplex Mode
Selection]
.
10
(10 - 102)
F7-16
(03F4)
Timeout Value
Sets the detection time for a communications timeout.
Note:
•
Set this parameter to
0.0
to disable the connection timeout function.
•
This parameter is not available in all 1000-series drives.
•
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0.0 s
(0.0 s - 30.0 s)
F7-17
(03F5)
EtherNet/IP Speed Scaling
Factor
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-18
(03F6)
EtherNet/IP Current Scale
Factor
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-19
(03F7)
EtherNet/IP Torque Scale
Factor
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-20
(03F8)
EtherNet/IP Power Scaling
Factor
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-21
(03F9)
EtherNet/IP Voltage Scale
Factor
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-22
(03FA)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2A (Hex.) Object.
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(-15 - 15)
F7-23 - F7-27
(03FB - 03FF)
F7-28 - F7-32
(0370 - 0374)
Dynamic Output Assembly
Parameters 1 to 10
Parameters used in Output Assemblies 116, 117, 118, 119, 120. Each parameter contains a
MEMOBUS/Modbus address. The value received for the Output Assembly will be written to this
corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means
that the value received for the Output Assembly will not be written to any MEMOBUS/Modbus
register.
0
(-)
F7-33 - F7-42
(0375 to 037E)
Dynamic Input Assembly
Parameters 1 to 10
Parameters used in Input Assemblies 166, 167, 168, 169, 170. Each parameter contains a
MEMOBUS/Modbus address. The value sent for the Input Assembly will be read from this
corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means
that the value sent for the Input Assembly is not defined by the user, therefore the option default
register value will be returned.
0
(-)
Table 6.1 Option Monitor
No.
Name
Description
Range
U6-80 - U6-83
Option IP Address 1 - 4
Shows the currently available local IP Address.
•
U6-80
: First octet
•
U6-81
: Second octet
•
U6-82
: Third octet
•
U6-83
: Forth octet
0 - 255
U6-84 - U6-87
Online Subnet 1 - 4
Shows the currently available subnet mask.
•
U6-84
: First octet
•
U6-85
: Second octet
•
U6-86
: Third octet
•
U6-87
: Forth octet
0 - 255
U6-88 - U6-91
Online Gateway 1 - 4
Shows the currently available gateway address.
•
U6-88
: First octet
•
U6-89
: Second octet
•
U6-90
: Third octet
•
U6-91
: Forth octet
0 - 255
U6-92
Online Speed
Shows CN1 Port 1 link speed currently available.
10: 10 Mbps
100: 100 Mbps