11 Input Assemblies (Converter Produces)
80
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Name
Description
NetCtrl
Run command is from network
0: Run command is not from network
1: Run command is from network
NetRef
Voltage command is from network
0: Voltage command is not from network
1: Voltage command is from network
State
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Voltage Actual
Actual Converter Voltage
Monitors the converter output voltage.
Speed actual data: Output Voltage x 2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
For example, when output voltage of 1024 with a voltage scale of 2:
Voltage actual data = 1024 x 2
2
= 4096 = 1000 (Hex.)
◆
EtherNet/IP Speed and Torque Control Input - 72 (0x48)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
72
0
0
-
-
-
-
-
Faulted
-
Running
1
-
1
2
Voltage Actual (Low Byte)
3
Voltage Actual (High Byte)
Name
Description
Running
Running
Faulted
Faulted
0: No Fault
1: Fault
Voltage Actual
Actual Converter Voltage
Monitors the converter output voltage.
Voltage actual data: Output Voltage x 2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
For example, when output voltage of 1024 with a voltage scale of 2:
Voltage actual data = 1024×2
2
= 4096 = 1000 (Hex.)
◆
EtherNet/IP Extended Speed and Torque Control Input - 73 (0x49)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
73
0
0
-
NetRef
NetCtrl
Ready
During
Regenerative
Operation
Running
Alarm
Faulted
1
State
1
2
Voltage Actual (Low Byte)
3
Voltage Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Fault
1: Fault
Alarm
Alarm
0: No Alarm
1: Alarm
Running
Running
During Regenerative Operation
During Regenerative Operation
Ready
Ready
0: Not Ready
1: Ready
NetCtrl
Run command is from network
0: Run command is not from network
1: Run command is from network