8 Output Assemblies (Drive Consumes)
38
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Assembly
Number
(Hex.)
Description
Type
Bytes
Page
70 (46)
EtherNet/IP Basic Speed Control Input
Input
4
71 (47)
EtherNet/IP Extended Speed Control Input
Input
4
72 (48)
EtherNet/IP Speed and Torque Control Input
Input
6
73 (49)
EtherNet/IP Extended Speed and Torque Control Input
Input
6
101 (65)
(Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Control Output
Output
8
115 (73)
(Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Control Output
Output
40
116 (74)
(Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Control Output
Output
44
117 (75)
(Vendor Specific Yaskawa Electric (YE) Assy) 8-Byte Dynamic Output 2
Output
8
118 (76)
(Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Output 4
Output
12
119 (77)
(Vendor Specific Yaskawa Electric (YE) Assy) 18-Byte Dynamic Output 7
Output
18
120 (78)
(Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Output 10
Output
24
151 (97)
(Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Status Input
Input
8
155 (9B)
(Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Status Input
Input
40
166 (A6)
(Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Status Input
Input
44
167 (A7)
(Vendor Specific Yaskawa Electric (YE) Assy) 8-Byte Dynamic Input 2
Input
8
168 (A8)
(Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input 4
Input
12
169 (A9)
(Vendor Specific Yaskawa Electric (YE) Assy) 18-Byte Dynamic Input 7
Input
18
170 (AA)
(Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input 10
Input
24
8
Output Assemblies (Drive Consumes)
Note:
The convention in this manual is from the PLC perspective. As such, an assembly is called an
“
Output Assembly
”
when outputted from
the PLC and received by this node. This section details
“
Output Assemblies
”
that are
“
Consumed
”
by the drive.
◆
EtherNet/IP Basic Speed Control Output - 20 (0x14)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
20
0
0
-
-
-
-
-
Fault Reset
-
Run Fwd
1
-
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
Fault Reset
0: -
1: Fault Reset
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2
SS
(SS: Speed scale)
Setting range: 0 - FFFF (Hex.)
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
2
= 1024 = 400 (Hex.)
Unit depends on o1-03.
◆
EtherNet/IP Extended Speed Control Output - 21 (0x15)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
21
0
0
-
NetRef
NetCtrl
-
-
Fault Reset
Run Rev
Run Fwd