11 Input Assemblies (Converter Produces)
90
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Name
Description
D1000: F7-34 Output Power
R1000: F7-34 Not Used
D1000: Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
R1000: -
F7-35 Terminal A2 Input
Programmable: MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
F7-36 Terminal S1 - S12
Programmable: MEMOBUS/Modbus (0x49)
Monitor parameter U1-10
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 18-Byte Dynamic Input 7 - 169
(0xA9)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
169
0
0
Faulted
Alarm
Ready
During Run -
Operation
Ready
Reset
During
Regenerative
Operation
-
Running
1
-
-
Multi-
Function
Digital
Output 3
Multi-
Function
Digital
Output 2
Multi-
Function
Digital
Output 1
LOCAL/
REMOTE
Uv
oPE
1
2
Output Voltage (Low Byte)
3
Output Voltage (High Byte)
2
4 - 5
Parameter [F7-33], Default: Alarm Code
3
6 - 7
D1000: Parameter [F7-34], Default: Output Power
R1000: Parameter [F7-34], Default: Not Used
4
8 - 9
Parameter [F7-35], Default: Terminal A2 Input
5
10 - 11
Parameter [F7-36], Default: Terminal S1 - S8 Input
6
12 - 13
Parameter [F7-37], Default: Terminal A3 Input
7
14 - 15
Parameter [F7-38], Default: Not Used
8
16
-
-
-
-
-
-
Parameter
[F7-39] (Low
Byte),
Default: Net
Ctrl
Parameter
[F7-39] (Low
Byte),
Default: Net
Ref
17
Parameter [F7-39] (High Byte), Default: Not Used
Name
Description
Running
Running
0: Stop
1: Running
During Regenerative Operation
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
Reset
0: -
1: Reset
During Run - Operation Ready
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage