11 Input Assemblies (Converter Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
79
Name
Description
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
D1000: Voltage Reference
R1000: -
D1000: Voltage Reference
Sets converter voltage reference.
R1000: -
Programmable Bytes
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter.
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be
written to any MEMOBUS/Modbus register.
11
Input Assemblies (Converter Produces)
Note:
The convention in this manual is from the PLC perspective. An
“
Input Assembly
”
is outputted from this node and read by the PLC. This
section details
“
Input Assemblies
”
that are
“
Produced
”
by the converter.
◆
EtherNet/IP Basic Speed Control Input - 70 (0x46)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
0
-
-
-
-
-
Faulted
-
Running
1
-
1
2
Voltage Actual (Low Byte)
3
Voltage Actual (High Byte)
Name
Description
Running
Running
Faulted
Faulted
0: No Fault
1: Fault
Voltage Actual
Actual Converter Voltage
Monitors the converter output voltage.
Voltage actual data: Output Voltage x 2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
For example, when output voltage of 1024 with a voltage scale of 2:
Voltage actual data = 1024×2
2
= 4096 = 1000 (Hex.)
◆
EtherNet/IP Extended Speed Control Input - 71 (0x47)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
0
0
-
NetRef
NetCtrl
Ready
During
Regenerative
Operation
Running
Alarm
Faulted
1
State
1
2
Voltage Actual (Low Byte)
3
Voltage Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Fault
1: Fault
Alarm
Alarm
0: No Alarm
1: Alarm
Running
Running
During Regenerative Operation
Converter in regenerative operation
Ready
Ready
0: Not Ready
1: Ready