11 Input Assemblies (Converter Produces)
92
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
6
12 - 13
Parameter [F7-37], Default: Terminal A3 Input
7
14 - 15
Parameter [F7-38], Default: Not Used
8
16
-
-
-
-
-
-
Parameter
[F7-39] (Low
Byte),
Default: Net
Ctrl
Parameter
[F7-39] (Low
Byte),
Default: Net
Ref
17
Parameter [F7-39], Default: Not Used (High Byte)
9
18 - 19
Parameter [F7-40], Default: Converter Software Version
10
20 - 21
Parameter [F7-41], Default: Not Used
11
22 - 23
Parameter [F7-42], Default: Not Used
Name
Description
Running
Running
0: Stop
1: Running
During Regenerative Operation
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
Reset
0: -
1: Reset
During Run - Operation Ready
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by converter model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Output Voltage
Converter Output Voltage