12 General Class Objects (Drive)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
99
Instance ID
Attribute
Name
Description
Get
Set
Size
Range
Default
1
6
Drive Mode
Drive Control Mode
0: OLV
0: OLV for PM (Read only)
0: Advanced OLV for PM (Read
only)
1: V/f
2: V/f with PG
3: CLV
3: CLV for PM (Read only)
Note:
On GA500, GA700, GA800,
HV600, and FP605, setting 1
also includes EZOLV (Read
only).
1: V/f Control, EZ Vector Control
○
○
Byte
0 - 3
0
1
7
Speed Actual
Actual Drive Speed
Unit depends on o1-03.
○
-
Word
-
3
1
8
Speed Reference
Speed Reference
Unit depends on o1-03.
○
○
Word
-
0
1
9
Current Actual
Actual Output Current
Monitors drive output current.
Unit is 0.01 A for drives set up to
11 kW in Heavy Duty or Normal
Duty and 0.1 A for drives set up
for 15 kW and above. The
maximum applicable motor output
varies depending on the setting of
C6-01 [Normal / Heavy Duty
Selection].
○
-
Word
-
0
1
11
Torque Actual
Drive Output Torque
Unit is affected by Torque Scale
(TS)
○
-
Word
-
0
1
12
Torque Reference/Torque
Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque
Limit. Unit is affected by Torque
Scale (TS)
Sets the Torque Reference when
using Torque Control [d5-01 = 1].
Sets the Torque Limit when using
Speed Control [d5-01 = 0].
The Torque Reference/Torque
Limit are disabled when F6-06 = 0.
○
○
Word
-
0
1
15
Power Actual [W]
Drive Output Power
Unit is affected by Power Scale
(PS).
○
-
Word
-
0
1
16
Input Voltage [V]
Drive Input Voltage [E1-01]
Unit is affected by Voltage Scale
(VS).
○
-
Word
-
Depends on
capacity
1
17
Output Voltage [V]
Drive Output Voltage
Unit is affected by Voltage Scale
(VS).
○
-
Word
-
0
1
18
Accel Time [ms]
Acceleration Time 1 [C1-01]
Units set in parameter C1-10.
Unit is affected by Time Scale
(TS).
○
○
Word
-
2710 (Hex.)
1
19
Decel Time [ms]
Acceleration Time 1 [C1-02]
Units set in parameter C1-10.
Unit is affected by Time Scale
(TS).
○
○
Word
-
2710 (Hex.)
1
20
Low Speed Limit Percent
of Max Speed
Frequency Reference Lower Limit
[d2-02]
○
○
Word
0 - 1100
0
1
21
High Speed Limit Percent
of Max Speed
Frequency Reference Upper Limit
[d2-01]
○
○
Word
0 - 1100
3E8 (Hex.)
1
22
Speed Scale (-15 - +15)
Scale of Units for Speed Related
Data
Sets or verifies
F7-17 [EtherNet/IP
Speed Scaling Factor]
.
○
○
Byte
-15 - +15
0
1
23
Current Scale (-15 - +15)
Scale of Units for Current Related
Data
Sets or verifies
F7-18 [EtherNet/IP
Current Scale Factor]
.
○
○
Byte
-15 - +15
0
1
24
Torque Scale (-15 - +15)
Scale of Units for Torque Related
Data
○
○
Byte
-15 - +15
0