14 Vendor-Specific (Yaskawa) Class Objects
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
109
Instance ID
Attribute
Name
Description
Get
Set
Size
Range
Default
1
9
Net Energy Odometer
The difference between Consumed
energy and Generated energy in
units of kWh.
○
-
SIGNED
ODOMETER
Array of 5
signed Words
-999,999,999,99
9.999 -
999,999,999,999
.999
-
1
10
Energy Transfer Rate
D1000: DC Bus power read from
U1-56 [DC Bus Side Power]
in
units of 1kW. In IEEE 754 REAL
format.
○
-
REAL
Depends on
capacity
-
1
12
Energy Type Specific
Object Path
EPATH to Electrical Energy Object
○
-
STRUCT of
UINT Size
Padded EPATH
-
Always 02 20
4F 24 01
◆
Electrical Energy Object 79 (Class 0x4F)
■
Services Supported
Service Code No. (Hex.)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
■
Attributes Supported
Instance ID
Attribute
Name
Description
Get
Set
Size
Range
Default
0
1
Electrical Energy
Software Revision
Electrical Energy Object software
revision
○
-
Word
-
2
1
1
Consumed Energy
Odometer
D1000: Consumed energy read
from
U9-01 [Electric Power
(GWh)]
to
U9-03 [Electric Power
(kWh)]
.
R1000: Always 0
○
-
ODOMETER
Array of 5
words
0 -
999,999,999,999
.999
-
1
2
Generated Energy
Odometer
Regenerative power read from
U9-
04 [Regenerative Power (GWh)]
to
U9-06 [Regenerative Power
(kWh)]
.
○
-
ODOMETER
Array of 5
words
0 -
999,999,999,999
.999
-
1
3
Net Energy Odometer
The difference between Consumed
energy and Generated energy in
units of kWh.
○
-
ODOMETER
Array of 5
signed Words
-999,999,999,99
9.999 -
999,999,999,999
.999
-
1
9
Line Frequency
Power supply frequency read from
U1-58 [Power Supply Frequency]
.
In IEEE 754 REAL format.
○
-
REAL
-
0
1
13
Average Current
Power supply current read from
U1-55 [Power Supply Current]
. In
IEEE 754 REAL format.
○
-
REAL
-
0
1
18
Average L-N Voltage
Power supply voltage read from
U1-54 [Power Supply Voltage]
. In
IEEE 754 REAL format.
○
-
REAL
-
0
1
39
Three Phase True Power
Factor
D1000: Power factor read from
U1-60 [Power Factor]
. In IEEE
754 REAL format.
○
-
REAL
-
0
1
41
Energy Type Specific
Object Path
EPATH to Base Energy Object
○
-
STRUCT of
UINT Size
Padded EPATH
-
Always 02 20
4E 24 01
14
Vendor-Specific (Yaskawa) Class Objects
◆
Yaskawa Drive Parameters Object - 100 (Class 0x64)
■
Services Supported
Service Code No. (Hex.)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Yaskawa Drive Parameters object is related to the parameters or monitor of Yaskawa drives. Not compatible with
EtherNet/IP compatible drives from a different company. With this Class object any drive parameter or monitor