Table 4.1 Male 8-way Ethernet Modular Connector (Customer-Supplied)
Male EtherNet 8-Way Modular Connector
Pin
Description
1 (Pair 2)
Transmit data (TXD) +
2 (Pair 2)
Transmit data (TXD) -
3 (Pair 3)
Receive data (RXD) +
4 (Pair 1)
Not used
5 (Pair 1)
Not used
6 (Pair 3)
Receive data (RXD) -
7 (Pair 4)
Not used
8 (Pair 4)
Not used
*1
Not used for 10 Mbps and 100 Mbps networks.
◆
Option LED States
The option has four LEDs:
•
Bi-color Status LEDs:
–
Module status (MS) red/green
–
Network status (NS) red/green
•
Ethernet LEDs:
–
Network speed-10/100 yellow
–
Link status and network activity-Link/Act green
A - 1000-Series, Z1000U
B - GA500, GA700, GA800
C - Z1000, HV600, and FP605
Figure 4.2 Option LED Labels
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for Z1000, HV600, or
FP605.
Wait 2 seconds minimum for the power-up diagnostic process to complete before you verify the LED states. The
shows the operating status of the option LEDs after the power-up diagnostic LED sequence is complete.
Refer to
for more information about the LEDs.
Table 4.2 Option LED States
LED Name
Indication
Operating State
Description
Color
Display
MS
-
OFF
Power supply off
There is no power to the drive.
Green
ON
Option operating
The option is operating normally.
Green
Flashing
Option initializing
The option is configuring an IP address.
Red
ON
Fatal error occurred
The option detected a fatal (unrecoverable) error.
Red
Flashing
Non-fatal error occurred
The option detected a non-fatal (recoverable) error.
Red/Green
Flashing
Option self-test
The option is in self-test mode.
NS
-
OFF
Power supply OFF or Offline
-
Green
ON
Online communications established
The option is online and has established connections.
Green
Flashing
Online communications not established
The option is online without an established connection.
Red
ON
Communications error (fatal)
The option detected a duplicate IP address.
Red
Flashing
Communications time-out (non-fatal)
A communications time-out occurred.
Red/Green
Flashing
Option self-test