10 Output Assemblies (Converter Consumes)
76
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Name
Description
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
Fault Reset
0: -
1: Fault Reset
Multi-Function Digital Output 1
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Multi-Function Digital Output 2
Terminals M3 and M4
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Multi-Function Digital Output 3
Terminals M5 and M6
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
D1000: Voltage Reference
R1000: -
D1000: Voltage Reference
Sets converter voltage reference.
R1000: -
Programmable Bytes
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter.
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be
written to any MEMOBUS/Modbus register.
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 18 Byte Dynamic 7 Output - 119
(0x77)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
119
0
0
Multi-
Function
Input 8
Multi-
Function
Input 7
Multi-
Function
Input 6
Multi-
Function
Input 5
Multi-
Function
Input 4
Multi-
Function
Input 3
D1000: -
R1000:
Forced Run
D1000: Run
R1000: Auto
Run
1
Multi-
Function
Digital
Output 3
Multi-
Function
Digital
Output 2
Multi-
Function
Digital
Output 1
-
-
-
Fault Reset
External Fault
1
2
D1000: Voltage Reference (Low Byte)
R1000: -
3
D1000: Voltage Reference (High Byte)
R1000: -
2
4 -5
Programmable Bytes [F7-23], Default: Not Used
3
6 -7
Programmable Bytes [F7-24], Default: Not Used
4
8 -9
Programmable Bytes [F7-25], Default: Not Used
5
10 -11
Programmable Bytes [F7-26], Default: Not Used
6
12 -13
Programmable Bytes [F7-27], Default: Not Used
7
14 -15
Programmable Bytes [F7-28], Default: Not Used
8
16 -17
Programmable Bytes [F7-29], Default: Not Used
Name
Description
D1000: Run
R1000: Auto Run
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
D1000: -
R1000: Forced Run
D1000: -
R1000: Force run converter
0: Stop
1: Force Run