11 Input Assemblies (Converter Produces)
88
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Name
Description
Running
Running
0: Stop
1: Running
During Regenerative Operation
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
Reset
0: -
1: Reset
During Run - Operation Ready
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by converter model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Output Voltage
Converter Output Voltage
F7-33 Alarm Code
Programmable: MEMOBUS/Modbus (0x7F)
D1000: F7-34 Output Power
R1000: F7-34 Not Used
D1000: Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
R1000: -
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input 4 - 168
(0xA8)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
168
0
0
Faulted
Alarm
Ready
During Run -
Operation
Ready
Reset
During
Regenerative
Operation
-
Running
1
-
-
Multi-
Function
Multi-
Function
Multi-
Function
LOCAL/
REMOTE
Uv
oPE