8 Output Assemblies (Drive Consumes)
46
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
Name
Description
Digital Outputs
MEMOBUS/Modbus (0x0009)
Note:
These values are ORed with values in byte 1.
Dynamic Outputs
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page
for more information.
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 8 Byte Dynamic Output - 117
(0x75)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
117
0
0
Multi-
Function
Input 8
Multi-
Function
Input 7
Multi-
Function
Input 6
Multi-
Function
Input 5
Multi-
Function
Input 4
Multi-
Function
Input 3
Run Rev
Run Fwd
1
Multi-
Function
Digital
Output 3
Multi-
Function
Digital
Output 2
Multi-
Function
Digital
Output 1
-
-
-
Fault Reset
External Fault
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
2
4 - 5
Dynamic Output 1 [F7-23], Default: Not Used
3
6 - 7
Dynamic Output 2 [F7-24], Default: Not Used
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Multi-Function Input 8
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
Fault Reset
0: -
1: Fault Reset
Multi-Function Digital Output 1
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF