9 Input Assemblies (Drive Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
63
Name
Description
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Fault Reset
Fault Reset
0: -
1: Fault Reset
Speed Agree
Speed Agree
0: -
1: Speed actual at speed reference
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Dynamic Inputs
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it will return the default data as defined in the table above.
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 18-Byte Dynamic Input - 169
(0xA9)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
169
0
0
Faulted
Alarm
Ready
Speed Agree
Fault Reset
REV Running
ZSP
Running