12 General Class Objects (Drive)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
93
Name
Description
F7-33 Alarm Code
Programmable: MEMOBUS/Modbus (0x7F)
D1000: F7-34 Output Power
R1000: F7-34 Not Used
D1000: Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
R1000: -
F7-35 Terminal A2 Input
Programmable: MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
F7-36 Terminal S1 - S12
Programmable: MEMOBUS/Modbus (0x49)
Monitor parameter U1-10
F7-37 Terminal A3 Input
Programmable: MEMOBUS/Modbus (0x50)
F7-38 Not Used
-
F7-39 NetRef (Status)
Voltage command is from network
0: Voltage command is not from network
1: Voltage command is from network
F7-39 NetCtrl
Run command is from network
0: Run command is not from network
1: Run command is from network
F7-39 Not Used
-
F7-40 Converter Software Version
Programmable: MEMOBUS/Modbus (0x4D)
Monitor parameter U1-25
F7-41 Not Used
-
F7-42 Not Used
-
12
General Class Objects (Drive)
◆
Identity Object - 1 (Class 0x01)
■
Services Supported
Service Code No. (hex)
Service Name
01
Get Attribute All
05
Reset
0E
Get Attribute Single
■
Attributes Supported
Instance ID
Attribute
Name
Description
Get
Set
Size
Range
Default
0
1
Object Software Revision Identity Object software revision
○
-
Word
-
1
1
1
Vendor ID
Manufacturer code.
44 (2C (Hex.)): Yaskawa Electric
○
-
Word
-
44
1
2
Device Type
Device profile.
The profile for this product is an
AC drive.
2: AC drive
○
-
Word
-
2
1
3
Product Code
Product codes determined by the
manufacturer.
○
-
Word
-
1
4
Revision
Software revision for the option.
○
-
Word
-
Depends on
software
1
5
Status
Shows the communication status
for the drive.
○
-
Word
-
0
1
6
Serial number
Option serial number.
○
-
Long
-
Each unit is
unique
1
7
Product Name
Product Name
○
-
String
-
Product
dependent
(i.e., CIMR-
AA2A0004)
1
8
State
Operation status of the drive.
3: Drive ready
4: Fault
○
-
Byte
-
3