9 Input Assemblies (Drive Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
57
Name
Description
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
ZSV
Zero Servo Completed
0: -
1: Zero Servo Completed
Motor Speed
Monitor parameter U1-05
Torque Actual
Output Torque
Shows the torque reference.
Value displays in 0.1% units.
PG Count Value
MEMOBUS/Modbus (0x7CD)
PG1 Count value register U6-18
Frequency Command
Monitor parameter U1-01
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Output Current
Actual Output Current
Monitors drive output current.
Unit: 0.01A
Unit is not affected by Current Scale CS.
Terminal A2 Input
MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
Main Circuit DC Voltage
Main Circuit DC Voltage
Monitor parameter U1-07
Error Alarm Signal 1
Error Alarm Signal 1
MEMOBUS/Modbus (0xC8)
Error Alarm Signal 2
Error Alarm Signal 2
MEMOBUS/Modbus (0xC9)
Error Alarm Signal 3
Error Alarm Signal 3
MEMOBUS/Modbus (0xCA)
Terminal A3 Input
MEMOBUS/Modbus (0x50)
Monitor parameter U1-15
Terminal S1 to S8 Input
MEMOBUS/Modbus (0x49)
Monitor parameter U1-10