11 Input Assemblies (Converter Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
91
Name
Description
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by converter model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Output Voltage
Converter Output Voltage
F7-33 Alarm Code
Programmable: MEMOBUS/Modbus (0x7F)
D1000: F7-34 Output Power
R1000: F7-34 Not Used
D1000: Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
R1000: -
F7-35 Terminal A2 Input
Programmable: MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
F7-36 Terminal S1 - S12
Programmable: MEMOBUS/Modbus (0x49)
Monitor parameter U1-10
F7-37 Terminal A3 Input
Programmable: MEMOBUS/Modbus (0x50)
F7-38 Not Used
-
F7-39 NetRef (Status)
Voltage command is from network
0: Voltage command is not from network
1: Voltage command is from network
F7-39 NetCtrl
Run command is from network
0: Run command is not from network
1: Run command is from network
F7-39 Not Used
-
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input 10 - 170
(0xAA)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
170
0
0
Faulted
Alarm
Ready
During Run -
Operation
Ready
Reset
During
Regenerative
Operation
-
Running
1
-
-
Multi-
Function
Digital
Output 3
Multi-
Function
Digital
Output 2
Multi-
Function
Digital
Output 1
LOCAL/
REMOTE
Uv
oPE
1
2
Output Voltage (Low Byte)
3
Output Voltage (High Byte)
2
4 -5
Parameter [F7-33], Default: Alarm Code
3
6 - 7
D1000: Parameter [F7-34], Default: Output Power
R1000: Parameter [F7-34], Default: Not Used
4
8 - 9
Parameter [F7-35], Default: Terminal A2 Input
5
10 - 11
Parameter [F7-36], Default: Terminal S1 - S8 Input