![Yamatake DigitroniK DCP32 User Manual Download Page 74](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225074.webp)
5-20
Chapter 5. FUNCTIONS
5 - 6
Output Processing Functions
Three outputs are provided as output processing functions: control output, SP output and auxiliary output.
■
MV1/MV2 switching
MV1 and MV2 according to control output or SP output, and outputs 1, 2 and 3
can be switched as shown in the figures below. (Processing in these figures
advances from left to right.)
●
0D, 5G output
●
2G output
●
3D, 5K output
Handling Precautions
• Switching of MV1 and MV2, and outputs 1, 2 and 3 can be selected in
setup data
C44.
• Switching of control output and SP output can be selected in setup data
C18 and C41.
• SP output can be output to current output other than heat output and
cool output.
• The “MV1/MV2 switching” function can be used for SP output even
though SP output originally is not MV. So, SP output is shown to be
connectable to MV1 and MV2 in the above figures for convenience only.
Channel 1 control output
Channel 1 SP output
MV1
Output 1
Channel 2 control output
Channel 2 SP output
MV2
Output 2
Auxiliary output
Output 3
Relay/current/voltage output
Current/voltage output
Current output
Channel 1 control output
Channel 1 SP output
MV1
Output 1 open-side output
Channel 2 control output
Channel 2 SP output
MV2
Output 3
Relay output
Output 1 closed-side output
Relay output
Current/voltage output
Channel 1 control output
Channel 1 SP output
MV1
Output 1: Heat output
Channel 2 control output
Channel 2 SP output
MV2
Output 3
Relay/current/voltage output
Output 2: Cool output
Relay/current/voltage output
Current/voltage output