2-10
Chapter 2. NAMES & FUNCTIONS OF PARTS
■
Input 2
●
Thermocouple
●
Resistance temperature detector (RTD)
●
DC current, DC voltage
Handling Precautions
• The unit of code Z06 is Kelvin (K)
• The lower limit readout of code B18 is 20°C.
The lower limit readout of codes K44, K46, T44, Z08 and Z07 is
-199.9°C.
• The lower limit readout of codes F50, F46, P50 and P46 is -199.9°C.
• The upper limit readout of codes F01 and P01 is 99.99°C.
• The PV lower limit alarm does not occur with code F50.
However, note that the PV lower limit alarm occurs at a line
disconnection if input has been downscaled when input is disconnected
during setup.
• The number of digits past the decimal point for DC current and DC
voltage is programmable within the range 0 to 3.
Input Type
Range No. Code
Temp. Range (°C)
Temp. Range (°F)
K (CA)
128
K44
-200.0 to +300.0
-300 to +700
K (CA)
129
K29
-200 to +1200
-300 to +2400
Input Type
Range No. Code
Temp. Range (°C)
Temp. Range (°F)
JIS’89Pt100
160
F36
-50.0 to +200.0
-50.0 to +400.0
(IEC Pt100
Ω
)
161
F01
0.00 to 100.00
0.0 to 200.0
JIS’89 JPt100
176
P36
-50.0 to +200.0
-50.0 to +400.0
177
P01
0.00 to 100.00
0.0 to 200.0
Input Type
Range No. Code
Range (programmable)
0 to 10 V
192
L07
-1999 to +9999
1 to 5 V
193
V01