![Yamatake DigitroniK DCP32 User Manual Download Page 161](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225161.webp)
8-13
Chapter 8. PROGRAM SETUP
■
Setting up PV start items
①
In the setting display state, move to the PV start items on the programming
map.
(The settings are common to all segments as the PV start items are setting items
provided for each program.)
②
If you press the
ENT
key, the lower display starts blinking to indicate start of
entry to the No.1 setup.
③
Press the
↑
,
↓
,
←
or
→
key to set to the No.1 setup PV start setting.
Setting range: 0 to 2
0: PV start disabled
1: PV start enabled on channel CH1
2: PV start enabled on channel CH2
④
When you press the
ENT
key, blinking on the lower display stops.
●
Display
• The settings are common to all segments as the PV start items are setting items
provided for each program.
• When setup data
C71
is set to 1, PV start items on the programming map are
skipped and not displayed.
• The profile display displays the trend of the SP pattern on the channel currently
selected in the basic display state.
PV start setting value
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out