Chapter 7. PARAMETER SETUP
Setting
0: Key lock disabled
1: Display of setup data settings disabled
2: Display of parameter settings and program settings disabled
3: Use of operation keys disabled
4: Display of parameter settings and program settings
displayed, and use of operation keys disabled
[Note]
Two or more key lock setting values for actual key lock items
and items assigned to the PARA key can be displayed and set.
0: Changing of program settings enabled
1: Changing of program settings disabled
0.0 to 120.0 seconds
[Note]
0.0 disables the filter.
-1000 to +1000U
-1999 to +9999U
0.0 to 10.0% (0.1% second steps)
[Note]
0.0 disables the limit.
0.0 to 100.0%
[Note]
On heat/cool models, the factory setting is 50.0.
0: Automatic judgment of initialization is carried out by advance
operation.
1: Initialization is carried out by advance operation.
2: Initialization is not carried out by advance operation.
0: AT is disabled.
1: General AT is executed.
2: Overshoot-inhibited AT is executed.
3: AT by neural net is executed.
[Note]
On heat/cool models when setup data
C44 setting is 0, “- - - -”
is displayed, and setting is not possible.
0: Smart-tuning is disabled.
1: The brake value is fixed to inhibit overshoot.
2: Overshoot is inhibited while automatically reviewing the
brake value.
[Note]
On heat/cool models when setup data
C44 setting is 0, “- - - -”
is displayed, and setting is not possible.
0: 2 degrees of freedom PID is disabled.
1: 2 degrees of freedom PID is enabled.
[Note]
On heat/cool models when setup data
C44 setting is 0, “- - - -”
is displayed, and setting is not possible.
0.1 to 60.0 seconds
-1999 to +9999U
[Note]
When setup data
C11 setting is 0 (PID set auto-switching
OFF), “- - - -” is displayed and setting is not possible.
-1999 to +9999U
[Note]
On heat/cool models when setup data
C44 setting is 0, “- - - -”
is displayed and setting is not possible.
On other models, when setup data
C11 setting is 0 (PID set
auto-switching OFF), “- - - -” is displayed and setting is not
possible.
0: 2X
1: 10X
2: 60X (10X)
3: 120X (10X)
[Note]
When setup data
C64 setting is 1 (program time unit:
minutes/seconds), the FAST factor is 10X for settings 2 and 3.
No. Item Code
Item
1
LoC
Key lock
2
PrtC
Program protect
3
FL
Input 1 digital filter
4
PbI
Input 1 bias
5
SbI
SP1 bias
6
otL
MV change limitter
(CH1)
7
IoUt
PID operation initial MV
8
rPId
PID operation
initialization
9
At
Auto-tuning method
selection (CH1)
10
St
Smart-tuning method
selection (CH1)
11
2PId
Advanced PID selection
(CH1)
12
gS.t
G.Soak time (CH1)
13
CP.11
PID auto-switching point 1-1
14
CP.12
PID auto-switching point 1-2
15
CP.13
PID auto-switching point 1-3
16
CP.14
PID auto-switching point 1-4
17
CP.15
PID auto-switching point 1-5
18
CP.16
PID auto-switching point 1-6
19
CP.17
PID auto-switching point 1-7
20
FASt
FAST factor
Factory
Setting
0
0
0.0
0U
0U
0.0
0.0
(50.0)
0
0
0
0
2.0
0U
200U
400U
600U
800U
1000U
1200U
0
User
Setting
7-7
■
Variable parameter settings “
PArA
”