8-6
Chapter 8. PROGRAM SETUP
■
Setting up SP2 items
①
In the setting display state, move to the SP2 item of the segment to be set up on
the programming map.
②
If you press the
ENT
key, the lower display starts blinking to indicate start of
entry to the No.1 setup.
③
Press the
↑
,
↓
,
←
or
→
key to set to the No.1 setup SP2 setting.
Setting range: SP2 lower to upper limit
(Set the SP2 limit in setup data
C32
or
C33
.)
④
When you press the
ENT
key, blinking on the lower display stops.
●
Display
■
Setting up events 1 to 3 items
●
When event type is PV type event
①
In the setting display state, move to the event 1 to 3 items of the segment to be
set up on the programming map.
②
If you press the
ENT
key, the upper display starts blinking to indicate start of
entry to the No.1 setup.
③
Press the
↑
,
↓
,
←
or
→
key to set to the No.1 setup event operating point
setting.
Setting range: -1999 to +9999U
0 to 9999U (in case of absolute value deviation event)
-10.0 to +110.0% (in case of MV, MFB event)
④
When you press the
ENT
key, blinking on the upper display stops.
(When the
FUNC
key + the
CLR
key are pressed, “- - - -” is redisplayed on the
upper display and blinking stops.)
●
Display (PV type event)
SP2 setting value
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
(CH 2)
EV1 to EV3 and T1 to T5 all out
Operating point setting value
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out