Chapter 5. FUNCTIONS
●
Controller status events
Controller status events are turned ON and OFF according to the DCP32 mode,
alarm status and other statuses.
Though the event standby function does not function, the ON delay function does.
Event setting values (operating point), hysteresis and event standby are not set.
• Basic operations
The following event types are provided:
RUN+HOLD+FAST+END
READY
RUN
HOLD
FAST
END
G.Soak standby (logical OR of CH1 and CH2, CH1, CH2)
MANUAL (logical OR of CH1 and CH2, CH1, CH2)
Auto-tuning executing (logical OR of CH1 and CH2, CH1, CH2)
Constant-value operation
MFB estimated position control
Logical OR of all alarms
PV range alarm
Controller alarms
Low battery voltage
Console setup in progress
Loader setup in progress
ADV
When the DCP32 reaches the state designated by the event type, the event is
turned ON. Otherwise, the event is OFF.
• Alarms
Alarms are divided into the PV range alarm group (alarm code Nos. 01 to 16)
and the controller alarm group (alarm code Nos. 70 to 99, and low battery
voltage).
When the event type is set to the logical OR of all alarms, the alarm turns ON
even if at least one of the alarms occurs.
When the event type is set to PV range alarm, the alarm turns ON even if at
least one of the alarms in the PV range alarm group occurs.
When the event type is set to controller alarm, the alarm turns ON even if at
least one of the alarms in the DCP32 alarm group occurs.
• ADV
This is ON for one second after executing program advance. The event ON
delay setting is also enabled.
●
Time events
When the event 1 to 3 type is set to time event, the event can be used in the same
way as time events 1 to 5. However, note that events 1 to 3 do not have segment
No. event functions.
Though the event standby function does not function, the ON delay function does.