7-33
Chapter 7. PARAMETER SETUP
Setting
-1999 to +9999U
[Note]
When the input 2 range type is non-linear, “- - - -” is displayed and
setting is not possible.
When the input 2 range type is changed from non-linear to linear, the
original non-linear range values remain.
The relationship between the analog inputs and readout values can
be inverted by inverting the upper and lower limit values.
0.0 to 10.0% (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 2 range type is non-linear, “- - - -” is displayed and
setting is not possible.
0: Disabled
1: Enabled
[Note]
Table data setting (
C, d) is used for the linearization table.
[Note]
“- - - -” is displayed and setting is not possible.
-1999 to upper limit U (PV2 channel model)
0.0 to upper %RH (temperature/humidity operation model)
[Note]
Changing the input 2 range has no effect on the range.
However, note that when a general reset is carried out, the value
becomes the 0%FS value of the input 2 range on PV2 channel
models, and 0.0%RH on temperature/humidity operation models.
Lower limit to 9999U (PV2 channel model)
Lower limit to 100.0%RH (temperature/humidity operation model)
[Note]
Changing the input 2 range has no effect on the range.
However, note that when a general reset is carried out, the value
becomes the 100%FS value of the input 2 range on PV2 channel
models, and 100.0%RH on temperature/humidity operation models.
0: OFF (PID set segment designation on CH2 side)
1: ON
[Note]
When set to 1, the CH2 side PID set item in the program is invalid.
The switching point for auto-switching is set in variable parameters
(
CP.21 to CP.27).
0: OFF
1: ON
[Note]
On temperature/humidity operation models, “- - - -” is displayed and
setting is not possible.
-10 to +110%
[Note]
On PV2 channel models, when
C35 setting is 0, “- - - -” is displayed
and setting is not possible.
0: Bump-less
1: Preset
[Note]
When the programmer function is selected, operation is bump-less
regardless of the setting of
C37.
-10 to +110%
[Note]
When
C37 setting is 0, “- - - -” is displayed and setting is not possible.
-10 to +110%
[Note]
This setting is invalid even if the DCP32 is selected for use as a
programmer with
C41 setting at 1.
On heat/cool modes, when
C44 setting is 1, the setting functions as
the MV (heat) setting in the READY mode.
No. Item Code
Item
25
C25
Input 2 range
lower limit (0%)
26
C26
Input 2 range
upper limit (100%)
27
C27
Input 2 root
extraction dropout
28
C28
Input 2
linearization table
approximation
29
C29
Unused
30
C30
Unused
31
C31
Unused
32
C32
SP2 lower limit
33
C33
SP2 upper limit
34
C34
PID set auto-
switching (CH2)
35
C35
PV2 setting at
input 2 over-range
(MV2)
36
C36
PV2 at input 2
over-range (MV2)
37
C37
Manual change
mode (MV2)
38
C38
Preset manual
value (MV2)
39
C39
MV in READY
mode (MV2, MV2
heat output)
Factory
Setting
Not
fixed
Not
fixed
0.0
0
—
—
—
0%FS
0.0
100%FS
100.0
0
0
0
0
0
0
User
Setting