8-15
Chapter 8. PROGRAM SETUP
■
Setting up pattern link items
①
In the setting display state, move to the pattern link items on the programming
map.
(The settings are common to all segments as the pattern link items are setting
items provided for each program.)
②
If you press the
ENT
key, the lower display starts blinking to indicate start of
entry to the No.1 setup.
③
Press the
↑
,
↓
,
←
or
→
key to set to the No.1 setup pattern link setting.
Setting range: 0 to 19
0:
Pattern link disabled
1 to 19: Pattern link destination program No.
④
When you press the
ENT
key, blinking on the lower display stops.
●
Display
• The settings are common to all segments as the pattern link items are setting
items provided for each program.
• When setup data
C71
is set to 1, pattern link items on the programming map are
skipped and not displayed.
• The profile display displays the trend of the SP pattern on the channel currently
selected in the basic display state.
Link destination program No.
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out