10-3
Chapter 10. SPECIFICATIONS
Item
Input 2
Scaling
Square root extraction
Linearization table approxi-
mation
Input bias
Digital filter
Number of inputs
Types of connectable out-
puts
Terminal voltage (open)
Terminal current (short-cir-
cuit)
Allowable contact resis-
tance (dry contact)
Residual current
(open-collector ON)
Leakage current
(open-collector OFF)
Parallel connection to other
instruments
Assignments (fixed)
Assignments (variable)
Input sampling cycle
ON detection min. hold
time
Upper display
Lower display
Program No. display
Segment No. display
Profile display
Status displays
Operation keys
Loader connector port
Mode
Program operation mode
Specification
-1999 to +9999U (settable by dc voltage range. Reverse scaling and decimal point
repositioning possible)
Dropout 0.1 to 10.0%, Possible by DC voltage range
12 (both line ends fixed, 11 points variable)
-1000 to +1000U variable
0.0 to 120.0 seconds variable (filter OFF at 0.0)
12
Dry contacts (relay contact) and open-collector (current sink to ground)
10.4 to 12.6 V (under operating conditions) across common terminal (terminal
) and
each input terminal
5.0 mA +6.6 mA across each terminal (under operating conditions)
ON:
700
Ω
max. (under operating conditions)
OFF:
10 k
Ω
min. (under operating conditions)
3 V max. (under operating conditions)
0.1 mA max. (under operating conditions)
Can be connected to Yamatake Corporation SDC40 and DCP30 series.
RUN, HOLD, RESET, ADV, program No.
FAST, PV start, AT, AUTO/MANUAL, G.Soak cancel, reverse/direct action
0.1 seconds
0.2 seconds (program No. 0.4 seconds)
Green 4-digit, 7-segment LED
This normally displays PV values. Item codes are displayed in parameter setup.
Orange 4-digit, 7-segment LED
This normally displays SP values and output value. Setting values are displayed in
parameter setup.
Green 2-digit, 7-segment LED
This normally displays program No.
Green 2-digit, 7-segment LED
This normally displays segment No. Item Nos. are displayed in parameter setup, and
alarm No. is displayed when alarm occurs.
6 orange LEDs
Displays program pattern rise, soak and fall tendencies.
24 round LEDs
Modes:
RUN, HLD, MAN, PRG (green)
Display details:
PV, SP, OUT, TM, CYC, CH1, CH2 (green)
Battery voltage: BAT (red) (blinks at low voltage)
Status:
AT, OT1, OT2, OT3 (orange)
Events:
EV1, EV2, EV3, T1, T2, T3, T4, T5 (orange)
13 rubber keys
1 (dedicated cable with stereo miniplugs)
READY:
Ready to run program (control stop/program No. selectable)
RUN:
Program run
HOLD:
Program hold
FAST:
Program fast-forward
END:
Program end
AUTO:
Automatic operation
MANUAL: Manual operation (output controlled on console)
25
External
Switch
(RSW)
Input
Indication
/Program-
mer