4-10
Chapter 4. WIRING
4 - 8
Connecting Control Outputs (outputs 1, 2, 3)
WARNING
Before wiring, or removing/mounting the DCP32, be sure to turn the power
OFF.
Failure to do so might cause electric shock.
15
14
13
31
11
12
16
Load
Power supply
Load (SSR)
Output 1 (MV1 or MV2)
Contact rating, resistive load
5 A (30 Vdc/120 Vac)
4 A (240 Vac)
Minimum switching current: 100 mA
Output 2 (MV2 or MV1)
• Current output
4 to 20 mA dc/0 to 20 mA
Resistive load 600
Ω
max.
• Voltage output
2 to 22 mA dc
With current adjustment function
(setup data
C79)
■
Relay output (0D)
Connect as follows:
15
14
13
31
11
12
16
Load
Load (SSR)
(SSR)
Output 1 (MV1 or MV2)
• Current output
4 to 20 mA dc/0 to 20 mA dc
Resistive load 600
Ω
max.
• Voltage output
2 to 22 mA dc
With current adjustment function
(setup data
C78)
Output 2 (MV2 or MV1)
• Current output
4 to 20 mA dc/0 to 20 mA dc
Resistive load 600
Ω
max.
• Voltage output
2 to 22 mA dc
With current adjustment function
(setup data
C79)
Handling Precautions
• When switching small currents, connect a bleeder resistor to allow
current flow of the minimum relay switching input (100 mA min.).
• Current output and voltage output can be selected by setup data
C 76.
Voltage output is reliant on an internal fixed-current circuit.
Set the current value in the setup data so that the optimum voltage is
obtained matched to the conditions of the SSR in use and the load.
Factory setting: general-purpose SSR voltage value.
• Internal connection of MV1 (CH1 MV) and MV2 (CH2 MV), and output 1
and output 2 can be selected in setup data
C44.
• 4 to 20 mA dc and 0 to 20 mA dc can be selected in setup data
C90.
■
Current output (5G)
Connect as follows.