Chapter 7. PARAMETER SETUP
Setting
-10 to +110%
[Note]
When
C12 setting is 0, “- - - -” is displayed and setting is not
possible.
0: Bump-less
1: Preset
[Note]
When the programmer function is selected, operation is bump-
less regardless of the setting of
C14.
-10 to +110%
[Note]
When
C14 setting is 0, “- - - -” is displayed and setting is not
possible.
-10 to +110%
[Note]
This setting is invalid even if the programmer function is
selected by
C18 setting.
On heat/cool models and setup data
C44 setting is 0, this
setting functions as the MV (heat) setting in the READY mode.
-10 to +110%
[Note]
When the model is not a heat/cool model, and setup data
C44
is set to 1 on a heat/cool model, “- - - -” is displayed and setting
is not possible.
0: MV1 output (controller function)
1: SP1 output (programmer function)
[Note]
“- - - -” is displayed and setting is not possible in the following
instances:
• 0D output:
C44 setting is 1 and C76 setting is 0
• 5G output:
C44 setting is 0 and C77 setting is 0
C44 setting is 1 and C76 setting is 0
• 2G/3D/5K:
C44 setting is 1 and C77 setting is 0
-1999 to +9999U
[Note]
When
C11 setting is 1 or 0, “- - - -” is displayed and setting is
not possible.
The relationship between the analog outputs and SP1 can be
inverted by inverting the upper and lower limit values.
0: Reverse action (heat, humidifying)
1: Direct action (cool, dehumidifying)
[Note]
On heat/cool models and setup data
C44 setting is 1 “- - - -” is
displayed and setting is not possible.
On other models, external switch input can invert direct/reverse
action on the setting of
C21.
0: °C
1: °F
[Note]
On PV2 channel models, when the input 2 range type is linear,
“- - - -” is displayed and setting is not possible.
128 to 193
128, 129: Thermocouple
160, 161, 176, 177: Resistance temperature detector
192, 193: Linear (DC current, DC voltage)
[Note]
Refer to the input 2 range table. Operation according to a
setting not listed in this table is not fixed.
0 to 3
[Note]
When the input 2 range type is non-linear, “- - - -” is displayed
and setting is not possible.
When the input 2 range type is changed from non-linear to
linear, the original non-linear range values remain.
No. Item Code
Item
13
C13
MV1 at input 1 over-
range
14
C14
Manual change mode
(MV1)
15
C15
Preset manual value
(MV1)
16
C16
MV in READY mode
(MV1, MV1 heat output)
17
C17
MV (cool) in READY
mode (MV1 cool output)
18
C18
Main output type (CH1)
19
C19
SP1 main output lower
limit (4 mA setting)
20
C20
SP1 main output upper
limit (20 mA setting)
21
C21
Control action (CH2)
22
C22
Input 2 temperature unit
23
C23
Input 2 range type
24
C24
Input 2 range decimal
point position
Factory
Setting
0
0
0
0
0
0
0U
1000U
0
0
128
Not
fixed
User