Program Setup
Programs can be set up when the DCP32 is in the basic display state. This is sometimes referred to as
“programming” in this manual.
If the DCP32 is not in the basic display state, press the
DISP
key to set the DCP32 to the basic display state.
Programming can be carried out more easily if the details of the setup are entered to the Programming Map Draft
Form at the end of this manual before starting programming.
■
How to enter program setup
●
Key operation
Press the
FUNC
key + the
PROG
key in the basic display state to enter program
setup.
In the program setup state, the
PRG
LED on the console lights, and the decimal
points in the program No. display and segment No. display light. However, note
that the DCP32 does not enter the program setup state in the following cases:
• When in the constant-value operation mode (when constant-value operation data
modE
setting is 1)
• When key lock is active (variable parameter
LoC
is set to 2 or 4)
Also, the setup cannot be changed even if the DCP32 is in the program setup in
the following case:
• When the program is protected (variable parameter
PrtC
is set to 1)
●
Display start items
When the DCP32 enters the program setup state, display starts from the program
No. and the segment No. pattern item.
■
Selecting the program No. to set up
There are two ways of selecting the program No. to set up:
• By selecting the program No. before entering program setup
• By selecting the program No. after entering program setup
●
Selecting the program No. before entering program setup
To select the program No. press the
PROG
key or
↓
if the DCP32 is in the basic
display state in the READY mode.
Handling Precautions
The program No. cannot be selected on the DCP32 when the program
No. is being selected by external switch inputs.
For details, see 6-3 Program Selection (page 6-17).
●
Selecting the program No. after entering program setup
Each press of the
FUNC
key + the
PROG
key in the program setup state
increments the program No. When 19 is reached, the program No. returns to 1.
Likewise, each press of the
FUNC
key +
↓
decrements the program No. When 1
is returned to, the program No. advances to 19.
However, note that when setup values are being entered (setting value is blinking)
during program setup, press the
ENT
key first to quit entry of values and then
press the
FUNC
key + the
PROG
key or the
FUNC
key +
↓
to change the
program No.
When you select the program No. by this method, the display changes to the
pattern item on the programming map.
This method can be used, for example, to select a program No. to set up a program
other than the No. being operated in the RUN mode. It can also be used to select a
program No. to set up a program other than the No. currently selected by external
switch input.