![Yamatake DigitroniK DCP32 User Manual Download Page 60](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225060.webp)
Chapter 5. FUNCTIONS
■
Time events 1 to 5
Either of time events or segment No. events can be selected by the time event type
item in the event configuration data setup.
●
Time events
The ON and OFF times or only the
ON time can be set for each event No.
and segment. The following describes
ON/OFF of output.
• When the ON time is smaller than
the OFF time, output is ON for the
duration from the ON time to the
OFF time.
(See segments 1, 6 and 7 in the
figure.)
• When only the ON time is set,
output is ON for the duration from
the ON time to the segment end
point.
(See segments 2 and 5 in the
figure.)
• When neither the ON time nor OFF
time are set, output is OFF.
(See segment 3 in the figure.)
• Setting only the OFF time without
an ON time is not possible.
(See segment 3B in the figure.)
• Setting an ON time to be greater to
or equal than the OFF time is not
possible.
(See segment 3C in the figure.)
• Only ON and OFF times set within
the segment time are valid. Times
straddling the next segment are
invalid. The ON and OFF times set
in the next segment are valid.
(See segments 4 and 5 in the
figure.)
Accordingly, the ON and OFF
times settings at the segment end
point are ignored.
However, ON and OFF times set
for segment end points when the
END mode is moved to are valid.
(See segment 9 in the figure, and
compare with segment 10 in the
END mode.)
• When the ON time is set to 0 (no
OFF time setting, or OFF time is
greater than 0), output becomes
OFF at time 0.
If output at the previous segment
end point was ON at this time, the
output status at the segment
switching point does not
momentarily become OFF.
(See segments 5 and 6 in the
figure.)
• The G.Soak standby time is not
included in the ON and OFF times.
(See segment 7 in the figure.)
Segment
1
ON time
OFF time
Output ON
Output OFF
ON<OFF
2
3
Output turns OFF at end of
segment even if OFF time is
not set.
Segment
ON time
OFF time
Output ON
Output OFF
3B
3C
ON=OFF ON>OFF
No ON
Segment
ON time
OFF time
Output ON
Output OFF
4
5
Segment time
Advance to segment 5
ON-OFF time is invalid even if
set in excess of segment 4 time.
Segment
ON time
OFF time
Output ON
Output OFF
5
6
ON=0
ON continued
Segment
ON time
OFF time
Output ON
Output OFF
7
G.Soak standby
Segment time start
Segment
ON time
OFF time
Output ON
Output OFF
5-6