5-13
Chapter 5. FUNCTIONS
●
RUN
In this mode, the program is running.
MV outputs are active in PID control, and events and time events are active.
In the program operation mode, program operation progresses according to the
elapsed time.
However, note that progress of program operation stops in the same way as the
HOLD mode when the DCP32 is in the G.Soak (Guarantee Soak) standby state.
●
HOLD
In this mode, program operation is held.
Progress of program operation stops. However, note that MV outputs are active in
PID control, and events and time events are active in the same way as in the RUN
mode.
The HOLD mode is not available during constant-value operation.
●
FAST
In this mode, the program is fast-forwarded.
This mode is like the RUN mode except that progress of the program operation
time is speeded up.
The time scale is selected by the variable parameter
FASt
setting.
MV outputs are active in PID control or ON-OFF control, and events and time
events are active.
The DCP32 does not enter the G.Soak standby state even if G.Soak (Guarantee
Soak) is set.
The FAST mode is not available during constant-value operation.
●
END
In this mode, operation of the program has ended.
MV outputs are active in PID control or ON-OFF control, and events and time
events are active with program operation stopped at the program end point.
The END mode is not available during constant-value operation.
●
AUTO
In this mode, program operation is automatic.
MV output is active according to control by the DCP32.
(However, note that when programmer functions are selected on the current output
channels except heat/cool, SP output is active according to controller control by
the DCP32.)
●
MANUAL
In this mode, program operation is manual.
MV output can be changed by
↑
,
↓
,
←
,
→
on the console or by communications.
(However, note that when programmer functions are selected on the current output
channels except heat/cool, SP output can be changed by
↑
,
↓
,
←
,
→
on the
console or communications.)